From b00c442e65300c0b62c8f8d17fc02067991ab244 Mon Sep 17 00:00:00 2001 From: David Schleef Date: Wed, 18 Jul 2001 08:15:41 +0000 Subject: [PATCH] Slap together some notes about insn_config --- Documentation/comedi/insn_config | 255 +++++++++++++++++++++++++++++++ 1 file changed, 255 insertions(+) create mode 100644 Documentation/comedi/insn_config diff --git a/Documentation/comedi/insn_config b/Documentation/comedi/insn_config new file mode 100644 index 00000000..8977f90f --- /dev/null +++ b/Documentation/comedi/insn_config @@ -0,0 +1,255 @@ + + +INSN_CONFIG: + +The first data element (data[0]) is an ID. + +Generic return values: + + Bad ID: EINVAL (should be EIO?) + Length is wrong: EINVAL + + EAGAIN: changed arguments, retry (like command_test) + + +Notes: + - Should we use the length as an ID? (no, cuz its dumb) + - Should there be a generic flags parameter? (no) + - Should trigger source configs return a token? (no) + - Would it be better to have a special subdevice for trigger + configuration? (no, because it goes against the "subdevices + are independent" design.) + - Should this configure generic triggers and return a token + to be put into a command, or configure specific triggers + that are tied to start_src, convert_src, etc.? + + +ID=0: COMEDI_INPUT +ID=1: COMEDI_OUTPUT +ID=2: open drain input (?) +ID=3: open drain output + + length=1 + chanspec is used to specify channel + type: SUBD_DIO + + These are used to configure the direction of digital I/O lines. + + Modifications: none + + Errors: none + + Notes: + - does open drain input make sense? + + +ID=xxx: analog output waveform generation + + Specify the number of samples in buffer. + +ID=xxx: analog triggering + + length=N + chanspec is ignored + type: any with cmd + + [0] - ID + [1] - analog trigger channel + [2] - flags + trigger + slope/level + hysteresis + [3] - high + + Modifications: ? + Errors: + - bad channel + - bad flags + - + Notes: + - are there devices that can specify debouncing? + - are there devices that can specify a time value after + which the analog trigger resets? + + +ID=xxx: simple digital triggering + + length = + chanspec is ignored + type: any with cmd + + [0] - ID + [1] - flags + trigger + edge/level + rising/falling + [2] - divider (?) + + Notes: + - should this configure pins, or configure triggers? + (ds: triggers, see independent subdevice design rule) + (ds: pins, because it makes other things easier) + - divider? (ds: too complicated. This is supposed to + be simple.) + - should this be encoded into the TRIG_EXT argument? + + +ID=xxx: extended digital triggering + + length = + chanspec: ignored + type: any with cmd + + [0] - ID + [1] - flags + trigger + + Notes: + - should this be the same as triggering for counter/timers? + + +ID=xxx: counter configuration + + The subdevice has an accumulator which changes based on + triggers. + + [0] - ID + [ ] - flags + generate command trigger when? + [1] - mode + [2] - source1_src + [3] - source1_arg + [4] - source2_src + [5] - source2_arg + [6] - gate_src + [7] - gate_arg + + Modes: + UP_COUNTER: + acc++ on source1 + + DOWN_COUNTER: + acc-- on source1 + + QUADRATURE: + acc+=atan(source1,source2) + + Notes: + - configuring pins vs. configuring triggers would make this + easier + + +ID=xxx: counter configuration, up counter + + chanspec: used to determine particular counter channel + + [0] - ID + [1] - flags + up/down + [2] - src (like command trigger) + [3] - arg + + Notes: + - too simple? no gating + +ID=xxx: counter configuration, up counter with gating +ID=xxx: counter configuration, quadrature + + +ID=xxx: command trigger, pattern matching + + [0] - ID + [1] - bit mask (1 - watch, 0 - don't watch) + [2] - bit pattern + + +ID=xxx: set software gate + [0] - ID + [1] - set/clear gate + + + + +Applications: + + - Pulse counting: + (STC: simple event counting) + + mode - up counter + primary source - external line (+/-) + + - Pulse counting with gate: + (STC: simple gated event counting) + + mode - up counter + primary source - external line + gate source - external line + + - Pulse length measurement: + (STC: single pulse-width measurement) + + mode - up counter with gate + primary source - timer + gate source - external line (+/-) + + latch and reset on gate (-) transition + + - Timestamping + (STC: buffered [non-]cumulative event counting, + single period measurement) + + mode - up counter + primary source - timer + secondary source - external line + + latch on secondary source (+) transition + + - Up/Down counter: + (STC: relative position sensing) + + mode - up/down counter + primary source - external line + secondary source - external line + + when(P)acc+=S?+1:-1 + + - Quadrature counting: + + mode - quadrature + primary source - external line 1 + secondary source - external line 2 + + - Frequency generation: + + mode - up counter + primary source - timer + + invert output on primary source trigger + + - Pulse generation + + (XXX needs work) + mode - dual up counter + primary source - timer + secondary source - timer + + set output on primary source trigger + clear output on secondary source trigger + + - Pulse Width Modulation + + same as above + secondary source - timer (latch arg) + + - Frequency Shift Keying: + + mode - double up counter + primary source - timer + secondary source - timer + gate - soft, or external line + + invert output on gate?primary:secondary source trigger + + - + + -- 2.26.2